Analog Input Settings; Analog Output Settings; Digital Input; External Power Source Connection And Fuse - Emerson Rosemount 3410 Series Retrofit Instructions

Hide thumbs Also See for Rosemount 3410 Series:
Table of Contents

Advertisement

3410 Communication and Output settings
February 2024
Figure C-9: PC to Meter Serial Connection Wiring
C.5 

Analog input settings

The Rosemount 3410 Series Ultrasonic Flow Meter has the capability to sample analog
temperature (Analog Input 1) and pressure (Analog Input 2) with 4-20 mA signals. These
analog input signals are configured to sink. The two independent analog input circuits
are configured for conventional 4-20 mA service. Also, 24 VDC isolated power supply
connection is provided for an external power source. Refer to the System Wiring Diagram
in .
C.6 

Analog output settings

The Rosemount 3410 Series Ultrasonic Flow Meter provides two 4-20 mA analog output
signals that are software configurable for either sink or source current. Refer to the System
Wiring Diagram in .
Full HART
which meets the specifications of the HART Communications Foundation can be connected
to a Rosemount 3410 Series Ultrasonic Flow Meter.
C.7 

Digital Input

The Rosemount 3410 Series Ultrasonic Flow Meter provides one digital input that can be
used as a general purpose input. The digital input must be configured via the MeterLink
Tools|Edit/Compare Configuration
C.8 

External power source connection and fuse

Located on the CPU Module are connections for a user-provided external power source,
a 2 Amp fuse and a 24 V loop power connection for ultrasonic meter analog outputs,
temperature transmitter or pressure transmitter devices. The current is limited to 88 mA.
70
functionality is provided so that any commercially available HART transmitter
®
screen.
Rosemount Gas Ultrasonic 3410 Series Electronics
Retrofit Instructions
00825-0300-3240