Analogue Outputs / 4; Digital Outputs; Digital Outputs And Logical Statuses - ProMinent DULCODOS ULIa Assembly And Operating Instructions Manual

Polymer preparation system
Table of Contents

Advertisement

17.1.4
Analogue outputs / 4 ... 20 mA
Output
Signal designation
Emulsion consumption output
polymer pump P3
17.1.5

Digital outputs

Output
Signal designation
Collective alarm
System ready for preparation >
Remote control via Pause
System in operation > Polymer solu‐
tion at the outlet
17.1.6

Digital outputs and logical statuses

Output
Signal designation
DO Q0.0
Stirrer P2
DO Q0.1
Polymer pump P3
DO Q0.2
Solenoid valve V1
DO Q0.3
Signal light/horn
DO Q0.4
Collective alarm
DO Q0.5
System ready for preparation >
Remote control via Pause
DO Q0.6
System in operation > Polymer solu‐
tion at the outlet
DO Q0.7
Booster pump P1 (optional)
For Comfort version
DO Q2.0
Automatic flushing valve V3 - outlet
DO Q2.1
Automatic flushing valve V2 -
drainage
Terminals
XDC5
1+2
Terminals
XDC4 1-3
XDC4 4-5
XDC4 6-7
Logical status✻
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Data sheets
Description
4 ... 20 mA = 4 h
Description
0 = Alarm
1 = System ready
1 = Polymer solution
Description
Stirrer OFF
Stirrer ON
Pump OFF
Pump ON
Solenoid valve closed
Solenoid valve open
Light/horn off
Light/horn on
Collective alarm enabled
no collective alarm
System NOT ready for
preparation
System ready for prepara‐
tion
System NOT operational
System operational
Pump error
Pump OK
Valve closed
Valve open
Valve closed
Valve open
97

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dulcodos ulia 400 basicDulcodos ulia 400 mediumDulcodos ulia 400 comfort

Table of Contents