Settings For Operating Mode (Set Menu); Settings For "Manual" Operating Mode; Settings For "Analogue" Operating Mode (Analg Menu) - ProMinent S2Ba Operating Instructions Manual

Sigma/ 2 metering pump
Table of Contents

Advertisement

Dulcodes UV-Desinfektionsanlage
®
ProMinent
Contact: for contact operation
(Identity code, control variant: external 1:1 / external with pulse control)
Batch: for batch operation
(Identity code, control variant: external with pulse control)
Analog
Manual
Batch
Contact
P
7.4

Settings for operating mode (SET menu)

NOTE
First select the operating mode in the MODE menu!
Exceptions: Timer and PROFIBUS
In the SET menu you can adjust various settings depending upon the selected operating mode.
The following programmable function settings menus appear in all operating modes:
Calibrate (CALIB menu)
Auxiliary frequency (AUX menu)
Flow (FLOW menu, available only if flow monitor is connected)
See also section 7.5!
Further settings menus depend upon the selected operating mode.
7.4.1

Settings for "manual" operating mode

There are no other settings menus in the overall SET menu for the "manual" operating mode
apart from those described in 7.5.
7.4.2

Settings for "analogue" operating mode (ANALG menu)

In addition to those settings menus described in 7.5, there is an additional ANALG menu in the
overall SET menu for the "analogue" operating mode.
The stroke rate is controlled by an analogue electrical signal via the "external control" terminal.
You can select three signal-processing methods:
0 - 20 mA:
at 0 mA the S2Ca does not operate
at 20 mA the S2Ca operates at 180 strokes/min.
Between these two extremes the stroke rate is proportional to the electrical
signal.
t e s
P
Continuous
display
Analog
Manual
P
Contact
Batch
®
.
n a
l a
Analog
P
Set
Set
- ANALOG
- MANUAL
- CONTACT
- BATCH
o
0 2
P
mA
Settings
Page 45