3.
To start calibration, press the
'Calibrate ...' menu item appears, the pump starts to pump
ð The
and indicates the number of strokes.
4.
After a reasonable number of strokes (a minimum of 200), use the
[Clickwheel] to stop the pump.
'Calibration ended' menu item appears. It requests you to
ð The
enter the calibration volume.
5.
Determine the required metering volume (difference between initial
volume - remaining volume in the measuring cylinder).
[Clickwheel] to enter this volume in the 'Calibration ended'
6.
Use the
menu items and close.
ð The pump switches to the
pump is calibrated.
[Clickwheel] .
7.
Press the
ð The pump returns to the
'Menu / Information è Settings è Inputs/outputs è ...'
'Inputs/outputs' menu splits into the following sub-menus:
The
'Auxiliary frequency'
1 -
2 -
'Relay1' (optional)
'Relay2' (optional)
3 -
'mA-Output' (optional)
4 -
'Flow monitor' (only if connected)
6 -
'Diaphragm rupture' (only if connected)
5 -
'Menu / Information è Settings è Inputs/outputs
Auxiliary frequency è ...'
è
The programmable function
to an auxiliary stroke rate, which can be set in the
menu.
It can be activated via the "External control" terminal. If the
frequency' is present, then the identifier "AUX" appears on the LCD
screen.
Refer to the "Hierarchy of Operating Modes, Functions and Fault Statuses"
for the order of the various operating modes, functions and fault statuses.
'Menu / Information è Settings è Inputs/outputs è Relay1 è ...'
The setting options for the 'Relay' function only exist if a
relay is fitted.
[Clickwheel] .
'Calibration result' menu item - the
'Menu / Information è Settings' menu.
'Auxiliary frequency' facilitates the switchover