Removing An I/O Module - WAGO 750 Series Manual

Hide thumbs Also See for 750 Series:
Table of Contents

Advertisement

Serie 750, 753
1. Use an operating tool to turn the DIN-rail locking cam until the nose of the DIN-rail
locking cam disengages from the DIN-rail.
2. Use the release tab to pull the head station off the DIN-rail and, if necessary, out of
the assembly. To remove head stations with two release tabs, both tabs must be
pulled at the same time!
ð When the head station is pulled out of an assembly, the electrical connections of the
data contacts or power jumper contacts to the subsequent I/O module are separated.

7.6 Removing an I/O Module

An I/O module can be detached from the DIN-rail with the help of its release tab and
pulled out of the assembly.
CAUTION
Risk of injury due to sharp-edged power jumper contacts!
Removing the products in a careless manner can cause cuts.
When removing the products, pay attention to the power jumper contacts!
Removing 750 Series I/O Modules
1. Pull the orange release tab on the I/O module upwards. To remove I/O modules with
two release tabs from an assembly, both tabs must be pulled at the same time!
System manual | Version: 3.3.1
Assembly and Disassembly
Figure 27: Disengage the locking cam
49