Alarms And System Messages; Alarm Messages - Siemens SITRANS F FC410 Operating Instructions Manual

Coriolis flowmeters with modbus
Table of Contents

Advertisement

Alarms and system messages

8.1

Alarm messages

In the following tables the bits for alarm group 1 and alarm group 2 can be found along with
possible causes and directions for corrective action.
Alarm group 1 (Modbus address 3012)
Bit
Diagnostic
4
Sensor supply volt. out of range
5
6
Temperature measurement fault
7
8
9
10
Flow values not valid
11
12
13
14
Invalid calibration data
15
Invalid compensation data
17
Malfunction in Pickup Amplitude
18
23
Malfunction in sensor driver
24
25
26
Unstable driver oscillation
27
Massflow out of specification
28
Volumeflow out of specification
29
Density out of specification
30
Fluid temp. below limit
31
Fluid temp. above limit
FC410 with Modbus
Operating Instructions, 02/2016, A5E33120874-AC
Action
Contact Siemens customer support
Contact Siemens customer support
Can be due to problems with measured fluid or hardware malfunction. If the
failure continues then contact Siemens customer support
Contact Siemens customer support for recalibration
Contact Siemens customer support
Contact Siemens customer support
Contact Siemens customer support
Contact Siemens customer support
Reduce the flow. If the failure continues then contact Siemens customer
support
Reduce the flow. If the failure continues then contact Siemens customer
support
Contact Siemens customer support
Increase the fluid temperature. If the failure continues then contact Siemens
customer support
Reduce the fluid temperature. If the failure continues then contact Siemens
customer support
8
79