Contact input signal 1 delay timer for reading
21.
Press the [▼] key. Displays screen for setting the Contact input signal 1 Delay timer
for reading.
Time for starting detection of the contact input signal 1 (sec) can be set.
●Setting range: 0 to 300sec. (Initial value: 0sec.)
Contact input signal 1 OFF detection timer
22.
Press the [▼] key.Displays screen for setting the OFF detection timer of Contact input
signal 1.
"Alarm AL25: Contact input signal 1 detection" is generated when the set time(sec) passed
from when the contact input signal 1 is not detected.
(When the signal is not detected for the set time, the alarm is generated)
●Setting range: 0 to 10sec. (Initial value: 0sec.)
Switching of the contact input signal 2
23.
Press the [▼] key. Displays screen for setting the operation for the Contact input signal
2.
Operation for alarm AL26: Contact input signal 2 detection can be selected.
Set value
OFF
WRN
FLT
HRR Series
Setting of the contact input signal 1 delay timer for reading
SEC
INP1 ⇒ DELAY( Alternately displayed )
Contact input signal 1 set value of the OFF
detection timer.
SEC
INP1 ⇒ OVER( Alternately displayed )
Operation of the contact input signal 2
INP2 ⇒ ALARM( Alternately displayed )
Contents
Alarm is not generated.
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the alarm
occurs.
Chapter 5 Display and Setting of Various Functions
HRX-OM-W002
Initial value
5.5 Advanced setting mode
5-41