SMC Networks HRR018-A-10 Series Operation Manual page 89

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

Output of the circulating fluid temperature drop alarm.
15.
Press the [▼] key. Displays screen for output setting of the circulating fluid temperature
drop alarm.
RUN
Output of alarm AL15: Circulating fluid temperature drop
Set value
ON
OFF
Switching of the ambient temperature alarm
16.
Press the [▼] key. Displays screen for changing the chiller behaviour when the
ambient temperature alarm occurs.
Displayed for air-cooled type only. (This item is not displayed for water-cooled type)
RUN
Operation for alarm AL11: Ambient temperature alarm can be selected.
Set value
OFF
WRN
FLT
Ambient temperature upper limit alarm
17.
Press the [▼] key. Displays screen for setting the upper limit of the ambient
temperature. Displayed for air-cooled type only. (This item is not displayed for
water-cooled type)
RUN
Upper limit of alarm AL11: Ambient temperature alarm can be changed.
Setting range: 5.0 to 45.0℃ (initial value: 40.0℃)
HRR Series
Output of the circulating fluid temperature drop alarm.
TEMP ⇒OUTLO ⇒ OUTP (Alternately displayed)
Contents
Contact output, or serial communication
signal is output.
Signal is not output.
Operation of the ambient temperature alarm
AMB ⇒ TEMP ⇒ ALARM ( Alternately displayed )
Contents
Alarm is not generated
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the alarm
occurs.
Ambient temperature upper limit alarm
AMB ⇒ HITMP ( Alternately displayed )
Chapter 5 Display and Setting of Various Functions
HRX-OM-W002
Initial value
Initial value
5.5 Advanced setting mode
5-39