Output of the circulating fluid temperature drop alarm.
15.
Press the [▼] key. Displays screen for output setting of the circulating fluid temperature
drop alarm.
RUN
Output of alarm AL15: Circulating fluid temperature drop
Set value
ON
OFF
Switching of the ambient temperature alarm
16.
Press the [▼] key. Displays screen for changing the chiller behaviour when the
ambient temperature alarm occurs.
Displayed for air-cooled type only. (This item is not displayed for water-cooled type)
RUN
Operation for alarm AL11: Ambient temperature alarm can be selected.
Set value
OFF
WRN
FLT
Ambient temperature upper limit alarm
17.
Press the [▼] key. Displays screen for setting the upper limit of the ambient
temperature. Displayed for air-cooled type only. (This item is not displayed for
water-cooled type)
RUN
Upper limit of alarm AL11: Ambient temperature alarm can be changed.
●
Setting range: 5.0 to 45.0℃ (initial value: 40.0℃)
HRR Series
Output of the circulating fluid temperature drop alarm.
TEMP ⇒OUTLO ⇒ OUTP (Alternately displayed)
Contents
Contact output, or serial communication
signal is output.
Signal is not output.
Operation of the ambient temperature alarm
AMB ⇒ TEMP ⇒ ALARM ( Alternately displayed )
Contents
Alarm is not generated
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the alarm
occurs.
℃
Ambient temperature upper limit alarm
AMB ⇒ HITMP ( Alternately displayed )
Chapter 5 Display and Setting of Various Functions
HRX-OM-W002
Initial value
○
―
Initial value
○
―
―
5.5 Advanced setting mode
5-39