SMC Networks HRR018-A-10 Series Operation Manual page 94

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

HRX-OM-W002
Chapter 5 Display and Setting of Various Functions
Table 5.5-1 List of alarms for which isolated pump operation is available
Alarm
Alarm name
no.
AL01
Low level in tank
AL02
Low level in tank
AL04
Water leakage
Circulating fluid discharge
AL09
pressure rise
AL10
Flow rate decreased
Ambient temperature is
AL11
out of the range
Electric conductivity
AL12
4
increase
AL13
NOT TEMP READY
Circulating fluid
AL14
temperature increase
Circulating fluid
AL15
temperature decrease
AL17
Low flow rate
High circulating fluid
AL18
discharge temp.
High circulating fluid
AL19
return temp.
High circulating fluid
AL21
discharge pressure
Low circulating fluid
AL22
discharge pressure
AL24
Memory error
Contact input 1 signal
AL25
detection
Contact input 2 signal
AL26
detection
AL27
Forced stop
AL28
Notice for maintenance
AL29
Communication error
AL30
Compressor circuit error
AL31
Sensor error
AL32
Controller error
1 Select from OFF/ WRN/ FLT. 2 Select from WRN/ FLT.
3 Can be set only for air-cooled type.
4 Option DM (Electric conductivity control type, de-ionized water piping type) only. Alarm is
automatically released when the electric conductivity returns within the range.
5 Select from OFF/ WRN.
6
Not generated for options Z.
7
Not generated for options Z and Z1.
5.5 Advanced setting mode
5-44
Initial
Upper line
value
(White)
FLT
AL01
WRN
AL02
6
1
AL04
WRN
2
AL09
FLT
7
1
AL10
WRN
1
AL11
OFF
3
5
AL12
WRN
1
AL13
OFF
1
AL14
OFF
1
AL15
OFF
7
1
AL17
FLT
FLT
AL18
FLT
AL19
FLT
AL21
FLT
AL22
FLT
AL24
1
AL25
FLT
1
AL26
FLT
FLT
AL27
1
AL28
OFF
1
AL29
WRN
FLT
AL30
FLT
AL31
FLT
AL32
Display
Lower line
(Green)
LOW⇒LEVEL⇒FLT
LOW⇒LEVE⇒WRN
WATER ⇒ LEAK
HIGH ⇒ PRESS
LOW⇒FLOW⇒WRN
AMB⇒TEMP⇒OUT
DI ⇒ ERROR
TEMP⇒READY⇒ERROR
TEMP⇒OUT.HI
TEMP⇒OUT.LO
LOW⇒FLOW⇒FLT
TEMP ⇒ FLT
RET⇒TEMP⇒FLT
HIGH⇒PRESS⇒FLT
LOW⇒PRESS⇒FLT
MEM ⇒ ERROR
INP1 ⇒ ERROR
INP2 ⇒ ERROR
FORCE ⇒ STOP
MANT ⇒ ALARM
COMM ⇒ ERROR
REF⇒ERROR⇒0000
SENS⇒ERROR⇒0000
CTRL⇒ERROR⇒0000
Alarms for which isolated
pump operation is
available
-
-
-
-
-
-
-
-
-
-
-
HRR Series

Advertisement

Table of Contents
loading

Table of Contents