SMC Networks HRR018-A-10 Series Operation Manual page 121

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

Alarm
Description
No.
AL01
Low level in tank
AL02
Low level in tank
6
AL04
Water leakage
Circulating fluid discharge
AL09
pressure rise
AL10
Flow rate decreased
Ambient temperature is
AL11
3
out of the range
Electric conductivity
AL12
4
increase
AL13
NOT TEMP READY
Circulating fluid
AL14
temperature increase
Circulating fluid
AL15
temperature decrease
7
AL17
Low flow rate
High circulating fluid
AL18
discharge temp.
High circulating fluid
AL19
return temp.
High circulating fluid
AL21
discharge pressure
Low circulating fluid
AL22
discharge pressure
AL24
Memory error
Contact input 1
AL25
signal detection
Contact input 2
AL26
signal detection
AL27
Forced stop
AL28
Notice for maintenance
AL29
Communication error
AL30
Compressor circuit error
AL31
Sensor error
AL32
Controller error
1 Selectable from OFF / WRN / FLT * 2 Selectable from WRN / FLT
3 Only air-cooled type can be set
4 Option DM 【With electric conductivity control function , DI water (pure water) piping】 only. When
entering the range, the alarm is released automatically.
5 Selectable from OFF / WRN
6 Not generated for option Z.
7 Not generated for options Z and Z1.
HRR Series
Table 7-1 Alarm code list and Troubleshooting
Initial value
Upper stage
(White)
FLT
AL01
WRN
AL02
1
AL04
WRN
2
AL09
FLT
7
1
AL10
WRN
1
AL11
OFF
5
AL12
WRN
1
AL13
OFF
1
AL14
OFF
1
AL15
OFF
1
AL17
FLT
FLT
AL18
FLT
AL19
FLT
AL21
FLT
AL22
FLT
AL24
1
AL25
FLT
1
AL26
FLT
FLT
AL27
1
AL28
OFF
1
AL29
WRN
FLT
AL30
FLT
AL31
FLT
AL32
Chapter 7 Alarm Notification and Troubleshooting
Display unit
Lower stage
(Press the reset key after eliminating the cause.)
(Green)
LOW⇒LEVEL⇒FLT
Fluid level shown by the fluid level meter has fallen.
Add circulating fluid.
LOW⇒LEVE⇒WRN
WATER ⇒ LEAK
Circulating fluid leakage inside the unit is suspected.
Piping resistance increased. Check the opening of the
HIGH ⇒ PRESS
valve, pinching or blockage of the piping or clogging of
the filter.
LOW⇒FLOW⇒WRN
Check the installation environment. Clean the dust filter
AMB⇒TEMP⇒OUT
of the ventilation.
DI ⇒ ERROR
Replace DI filter.
TEMP⇒READY⇒ERROR
Overloaded, cooling failure, insufficient circulating fluid
flow rate, large fluctuation of the heat load, etc.
TEMP⇒OUT.HI
Increase the flow rate through the chiller. (Adjust the by-
pass valve)
TEMP⇒OUT.LO
Displayed flow rate: 2LPM or less, piping is thin,
LOW⇒FLOW⇒FLT
external valve is closed, pinching or blockage of the
piping or clogging of the filter.
Discharge temp.: 45
TEMP ⇒ FLT
failure, insufficient flow rate, etc. Increase the flow rate
through the chiller. (Adjust the by-pass valve)
Return temp.: 45
RET⇒TEMP⇒FLT
rate, overload, etc. Increase the flow rate through the
chiller. (Adjust the by-pass valve)
Displayed pressure: 0.5MPa or higher. Connect piping
HIGH⇒PRESS⇒FLT
so that the pressure is 0.5MPa or less. Adjust the
bypass valve.
Displayed pressure:0.03MPa or less.
LOW⇒PRESS⇒FLT
Check that the pump has not stopped.
Turn off the power supply switch and restart.
MEM ⇒ ERROR
If the error occurs again, ask for service.
INP1 ⇒ ERROR
Contact input has been detected.
INP2 ⇒ ERROR
Isolated operation of the pump is stopped (press
FORCE ⇒ STOP
"RUN/STOP" key for 5 seconds).
Notice for maintenance, perform maintenance for part
MANT ⇒ ALARM
for which alarm is generated.
No request message from the host computer.
COMM ⇒ ERROR
Try to send the request message again.
REF⇒ERROR⇒0000
Error occurred in the refrigerated circuit. Ask for service.
SENS⇒ERROR⇒0000
An error occurred in a sensor. Ask for service.
CTRL⇒ERROR⇒0000
An error occurred in the controller. Ask for service.
HRX-OM-W002
Cause / Remedy
o
C or higher. Overload, cooling
o
C or higher. Insufficient chiller flow
7.3 Troubleshooting
7-5