SMC Networks HRR018-A-10 Series Operation Manual page 102

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

HRX-OM-W002
Chapter 5 Display and Setting of Various Functions
Contact output signal 2 Operation
18.
Press the [▼] key. Displays screen for setting the operation of the Contact output
signal 2.
Select the Contact output signal 2 operation.
Contact output signal 2 Select alarm
19.
Press the [▼] key. Displays screen for setting the selected alarm of the Contact output
signal 2.The alarm is valid when the "selected alarm status signal output" is active.
Select the alarm No. to be allocated to Contact output signal 2
●Setting range: AL.01 to AL.32 (Initial value: AL.01)
Contact output signal 2 Select maintenance
20.
Press the [▼] key. Displays screen for setting the selected maintenance of the Contact
output signal 2. The alarm is valid when the "selected maintenance status signal output"
is selected.
Select the maintenance alarm No. to be allocated to Contact output signal 2.
● Setting range: MT.01 to MT.05 (Initial value: MT.01)
Contact output signal 3 Select function
21.
Press the [▼] key. Displays screen for setting the function of the Contact output signal
3.
5.5 Advanced setting mode
5-52
Contact output signal 2 operation
DOUT ⇒ SEL( Alternately displayed )
Set value
Contents
A
N.O. type
B
N.C. type
Contact output signal 2 Selected alarm No.
DOUT2 ⇒ ALARM ⇒ CODE( Alternately displayed )
Contact output signal 2 Selected maintenance alarm No.
DOUT2 ⇒ MANT ⇒ CODE( Alternately displayed )
Contact output signal 3 function
DOUT3 ⇒ SEL( Alternately displayed )
Initial value
HRR Series