SMC Networks HRR018-A-10 Series Operation Manual page 81

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

State ⑤: Temperature monitoring enters the upper and lower limit range, "TEMP OUT" output OFF.
State ⑥: Since the temperature range is again within the monitoring
range, "AL.14" will not be reported and "TEMP OUT" Output OFF continues.
State ⑦: AL.14 report since 45 sec has elapsed since the circulating fluid temperature deviated,
because it is outside the upper temperature monitoring range. TEMP OUT output ON.
State ⑧: The alarm is reset manually, the temperature monitoring upper and lower limit range is out,
so "AL.14", "AL.15" warning continue.
State ⑨: Since it is within the temperature monitoring upper limit range, "TEMP OUT" output OFF
State ⑩: Manual reset of alarm "AL.14", "AL.15" cancellation.
Low temperature limit of temperature range monitoring function
22.
Press the [▼] key. Displays Low temperature limit of temperature range monitoring
function setting screen.
RUN
For the function, refer to P.5-29,P.5-30 [Temperature range monitoring function setting
example].
Monitoring of temperature range monitoring function
23.
Press the [▼] key. Displays monitoring of temperature range monitoring function
setting screen
RUN
Please select from the following items.
Set value
RNST
PWON
For the function, refer to P.5-29,P.5-30 [Temperature range monitoring function
setting example].
HRR Series
Low temperature limit of temperature range monitoring function
( Setting range :1.0 to 40.0℃)
TEMP ⇒ OUT ⇒ LOTMP( Alternately displayed )
Monitoring of temperature range monitoring function
TEMP ⇒ OUT ⇒ALARM( Alternately displayed )
Monitoring during operation: The function is effective only
during operation.
Always Monitoring: The function is enabled even when
stopped (standby state).
Chapter 5 Display and Setting of Various Functions
Contents
HRX-OM-W002
5.5 Advanced setting mode
5-31