SMC Networks HRR018-A-10 Series Operation Manual page 132

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

HRX-OM-W002
Chapter 8 Control, Inspection, Exchange and Cleaning
3.
Blow out circulating fluid inside of piping of this product by air blow.Blow air (pressere: 0.1
MPa or less, about one minite) from circulating fluid returen port.The fluid will come out from
drain port and circulating fluid outlet.When executing this operation, tank cap should be
closed and bypass valve should be opened.
Air blow
(Pressure 0.1 MPa
or less)
Container
4.
Particle filter is installed inside of this product.Discharge circulating fluid from inside of filter
case.Remove filter panel holding screws by using cross slot screw driver and remove the
filter panel.
Filter panel
8.3 Stop for a Long Time
8-10
Circulating fluid return port
Circulating fluid outlet port
Holding screw
HRR Series