 Power supply specifications, power supply cable and earth leakage breaker
Prepare the power supply shown in the following table. For the connection between the product and
power supply, use the power supply cable and earth leakage breaker shown below. An earth leakage
breaker must be mounted to a position where the breaker is easily accessible and close to the
thermo-chiller.
Table 3-3 Power supply cable and earth leakage breaker (
Model
(High pump head
[Optional])
HRR012-A/W-10-
HRR018-A/W-10-
HRR012-A/W-20-
HRR018-A/W-20-
HRR024-A/W-20-
HRR030-A/W-20-
HRR012-A/W-20-T
HRR018-A/W-20-T
HRR024-A/W-20-T
HRR030-A/W-20-T
 Installation/operation in accordance with the UL standard (for the optional UL
compliant model)
For operation of the UL compliant model (available as an option,
HRR012/018/024/030-A/W-10/20-U) in the UL compliant conditions, the conditions shown below
must be satisfied:
● Use power supply of overvoltage category 2 (transient overvoltage 2500 V or less)
1 When using a power supply in the overvoltage category 3, take measures such as
mounting an isolation transformer between the product and the power supply or keep the
transient overvoltage of the power supply to 2500 V or less by using a varistor, etc.
HRR Series
Power supply
voltage
1-phase
AC100V (50/60Hz)
1-phase
AC115V (60Hz)
3 cores x
(3 cores x
1-phase
(including
200-230V AC
(50/60Hz)
Chapter 3 Transport and Setting Up
Recommended
Recommended earth
leakage breaker
Cable
qty.
Rated
x size
voltage
[V]
100,
115
14AWG
2
2.0mm
)
200,
230
ground)
HRX-OM-W002
)
Sensitivity
Rated
of leak
current
current
(A)
[mA]
15
30
10
30
15
30
 1
3.3 Installation
3-9

Advertisement

Table of Contents
loading