HRX-OM-W002
Chapter 9 Documents
1: Use the product in conditions where freezing will not occur. Consult with SMC if using in a season or region where
the ambient temperature will fall below zero.
2: If tap water is used, use water which satisfies the standard of The Japan Refrigeration And Air Conditioning
Industry Association (JRA GL-02-1994/Cooling water system –circulation type - make-up water).
3: (1)Facility water temp: 25℃, (2)Circulating fluid temp: 20℃, (3) Criculating fluid rated flow,(4) Criculating fluid : Tap
water, (5)Power supply : 100V type:AC100V, 200V type AC200V,(6)Piping length : Shortest
The cooling capacity will be reduced by 300W when option T and MT [High pressure pump] are selected.
4: (1)Ambient temp.: 25℃, (2)Facility water temp: 25℃, (3)Circulating fluid temp.: 20℃, (4)Circulating fluid rated flow,
(5)Criculating fluid : Tap water,(6)Power supply : 100V type:AC100V, 200V type AC200V, (7)Piping length :
Shortest
5: Outlet temp. when the circulating fluid flow is rated flow, and the circulating fluid outlet and the return are directly
connected.Installation environment and power supply are within specification range and stable.
6: The capacity at the thermo-chiller outlet when the circulating fluid temp. is 20℃.
7: Fluid flow to maintain the cooling capacity and the temperature stability.
The specification of the coolong capacity and the temperature stability may not be satisfied if the flow rate is lower
than the rated flow.
8: To be prepared by the customer. Use an earth 30mA/100V type :AC100V, 200V type : 200V in power supply
specification.
9: Front 1m/Height 1m/Static with no load. See note 3 for other conditions.
10: Dimension between panels. Projection is not included.
When option Y[With feet, and no Rack Mounting bracket] is selected, refer to [6.4. Option Y【With feet and no
Rack Mounting bracket】].
11: Weight when the circulating fluid is not included. The weight will increase by 1kg when
option DM [Electric conductivity control + Applicable to deionized water piping] is selected. The weight will
increase by 5kg when option T [High pressure pump] and MT [Applicable to deionized water piping + High
pressure pump]are selected.
The weight will decrease by 1kg when option Z.
12: Copper and brass are not included when option M [Applicable to deionized water piping] and MT [Applicable to
deionized water piping + High pressure pump] is selected.
13: When option DM [Electric conductivity control + Applicable to deionized water piping] is selected, these materials
are included.
14: Required flow rate when a load for the cooling capacity is applied at a condition of note 3.
15: If the altitude is 1000 m or more, please refer to "P.3-3 When Thermo-chiller installation in high altitude of 1000
meters or more".
16: No continuous voltage flucuation.
17: To be prepared by the customer.
18: When option T [High pressure pump] is selected, these materials are included.
19: (1)Ambient temp: 25℃, (2)Circulating fluid temp: 20℃, (3) Circulating fluid rated flow, (4) Circulating fluid : Tap
water, (5)Power supply: 100V type:AC100V, 200V type AC200V, (6)Piping length: Shortest, (7)Rated cooling load
is applied.
20: When Option DM[Electric conductivity control + Applicable to deionized water piping] is selected, DI filter will be
added.
Piping thread type : When F is selected, G thread adapter set will be added.
Piping thread type : When N is selected, NPT thread adapter set will be added.
Not included for options Z and Z1.
21: 200V type manufactured befor August 2019
22: 200V type manufactured befor August 2019
9.1 Specifications
9-4
can not be set below 10℃.
(Serial:XV)
can not be set below 5μS/cm.
(Serial:XV)
HRR Series