Displays the function of the Contact output signal 3.
Set value
No output signal
Operation status signal output
Remote status signal output
Unused
Ready completion (TEMP READY) signal output
TEMP OUT (temperature is out of the range) signal output
FLT (operation stop) alarm signal output
WRN (operation continue alarm) signal output
Notice for maintenance signal output
Alarm status signal output
Pass through signal of the contact input signal 1
Pass through signal of the contact input signal 2
Selected alarm status signal output
Selected notice for maintenance signal output
Contact output signal 3
22.
Press the [▼] key. Displays screen for setting the operation of the Contact output
signal 3.
Contact output signal 3 operation
Contact output signal 3 Select alarm
23.
Press the [▼] key. Displays screen for setting the selected alarm of Contact output
signal 3. The alarm is valid when the "selected alarm status signal output" is active.
Select the alarm No. to be allocated to Contact output signal 3
●Setting range: AL.01 to AL32 (Initial value: AL01)
HRR Series
Explanation
Operation
Contact output signal 3 operation
DOUT ⇒ TYPE( Alternately displayed )
Set value
Contents
A
N.O. type
B
N.C. type
Contact output signal 3 Selected alarm No.
DOUT3 ⇒ ALARM ⇒ CODE( Alternately displayed )
Chapter 5 Display and Setting of Various Functions
Initial value
HRX-OM-W002
Initial value
(Default setting)
5.5 Advanced setting mode
5-53