Temperature for pump to continue operation when alarm is generated.
29.
Press the [▼] key. Displays screen for setting the upper limit of temperature for the
pump to continue operation when an alarm is generated.
●Setting range: 5.0 to 45.0℃ (initial value: 40.0℃)
Refer to P.5-43 "Isolated operation of the pump" for settings.
Switching of the notice for maintenance
30.
Press the [▼] key. Displays screen for setting the switching of the notice for
maintenance. Alarm AL28: Notice for maintenance is generated.
Operation for alarm AL28: Notice for maintenance can be selected.
Set value
OFF
WRN
FLT
Switching of the Flow rate failure alarm
31.
Press the [▼] key. Displays screen for setting the switching of the Flow rate failure
Alarm. (In the case of option Z, Z1, this item will not be displayed.)
Operation for alarm AL17: Flow rate failure can be selected.
Set value
OFF
WRN
FLT
 Can be set from the serial "YR "
HRR Series
Upper limit of the circulating fluid temperature for isolated
operation of the pump
PUMP ⇒ TEMP (Alternately displayed)
Notice for maintenance
MANT ⇒ ALARM (Alternately displayed)
Contents
Alarm is not generated. Only "X" is displayed
when a notice for maintenance is generated.
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the
alarm occurs.
Operation for Flow rate failure alarm.
LOW ⇒ FLOW ⇒ ALARM (Alternately displayed)
Contents
Alarm is not generated.
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the
alarm occurs.
Chapter 5 Display and Setting of Various Functions
HRX-OM-W002
Initial value
Initial value
5.5 Advanced setting mode
5-45