SMC Networks HRR018-A-10 Series Operation Manual page 92

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

HRX-OM-W002
Chapter 5 Display and Setting of Various Functions
Contact input signal 2 delay timer
24.
Press the [▼] key. Displays screen for setting the Contact input signal 2 detection
delay timer for reading.
Time for starting detection of the contact input signal 2 (sec) can be set.
●Setting range: 0 to 300sec. (Initial value: 0sec.)
Contact input signal 2 OFF detection time
25.
Press the [▼] key. Displays screen for setting the contact input signal 2 OFF detection
timer.
"Alarm AL26: Contact input signal 2 detection" is generated when the set time(sec) passed
from when the contact input signal 2 is not detected.
(When the signal is not detected for the set time, alarm is generated)
●Setting range: 0 to 10sec. (Initial value: 0sec.)
Switching of communication error alarm
26.
Press the [▼] key. Displays screen for setting the communication error alarm
operation.
Operation for alarm AL29: Communication error can be selected.
Set value
OFF
WRN
FLT
5.5 Advanced setting mode
5-42
Setting of the contact input signal 2 delay
timer for reading
SEC
INP2⇒ DELAY( Alternately displayed )
Contact input signal2 set value of the OFF
detection timer.
SEC
INP2 ⇒ OVER( Alternately displayed )
Operation for communication error alarm
COMM ⇒ ALARM( Alternately displayed )
Contents
Alarm is not generated.
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the alarm
occurs.
Initial value
HRR Series

Advertisement

Table of Contents
loading

Table of Contents