Example of MODE 3
When the offset temperature is 1
(circulating fluid set temperature + offset temperature) Even if the discharge temperature is
o
31
C, the circulating fluid temperature is 30
heat radiation during sending of the fluid. The circulating fluid display temperature and the
communication data is 30
circulating fluid temperature at the customer's device.
To switch the offset mode, press the [ENT] key. "OFF" flashes,
press the [▲], [▼] key, select "OFF", "MD1", "MD2", "MD3" and confirm with [ENT] key.
Offset temperature
7.
Press the [▼] key. Displays offset temperature setting screen.
RUN
To change the offset temperature, press the [ENT] key. "0.0" flashes,press the [▲], [▼] key to
change the offset temperature.
When the [ENT] key is pressed, the flashing ends and the offset temperature is fixed.
HRR Series
This produuct
Circulating fluid
temperature 29℃
Serial communication
Discharge
temperature 30℃
Circulating fluid display
temperature
29℃
Circulating fluid set
temperature
30℃
Offset temperature
-1℃
o
C, the thermo-chiller controls the temperature at 31
o
C (circulating fluid discharge temp. - offset temp.), and matches the
This produuct
Circulating fluid
temperature 30℃
Serial communication
Discharge
temperature 31℃
Circulating fluid display
temperature
30℃
Circulating fluid set
temperature
30℃
Offset temperature
1℃
Offset temperature:Set within the range of -20.0 to 20.0°C
OFSET ⇒ TEMP ( Alternately displayed )
Chapter 5 Display and Setting of Various Functions
Your system
Heat
radiation
1℃
29℃
o
C at the customer's device because of 1
Your system
Heat
radiation
1℃
30℃
HRX-OM-W002
o
C
o
C of
5.5 Advanced setting mode
5-23