The water cooled product radiates heat to the facility water.
It is necessary to supply the facility water. Please prepare the facility
water system that satisfies the heat radiation and the facility water
specifications below.
 Required facility water system (for water cooled type)
Model
Radiated
HRR012-W-10/20-
HRR018-W-10/20-
HRR024-W-10/20-
HRR030-W-10/20-
HRR Series
Facility water source to be prepared
Table 3-2
Heat
Facility water temp.
kW
Approx.2
Approx.4
Approx.5
(Rating 25)
Approx.6
Required facility water flow rate
range
o
C
5 to 40
HRX-OM-W002
Chapter 3 Transport and Setting Up
l/min
Facility water temprature
25℃
32℃
8
12
12
15
14
17
15
18
3.2 Installation
40℃
20
23
25
26