SMC Networks HRR018-A-10 Series Operation Manual page 90

Thermo-chiller
Hide thumbs Also See for HRR018-A-10 Series:
Table of Contents

Advertisement

HRX-OM-W002
Chapter 5 Display and Setting of Various Functions
Ambient temperature lower limit alarm
18.
Press the [▼] key. Displays screen for setting the lower limit of the ambient
temperature alarm.
Displayed for air-cooled type only. (This item is not displayed for water-cooled type)
RUN
Lower limit of alarm AL11: Ambient temperature alarm can be changed.
●Setting range: 5.0 to 40.0℃ (initial value: 10.0℃)
Switching of the leakage alarm
19.
Press the [▼] key. Displays screen for setting the leakage alarm operation.
(In the case of option Z, this item will not be displayed.)
RUN
Operation for alarm AL04: Leakage alarm can be selected.
Set value
OFF
WRN
FLT
Switching of the contact input signal 1
20.
Press the [▼] key. Displays screen for setting the operation of the Contact input signal
1.
Operation for alarm AL25: Contact input signal 1 detection can be selected.
Set value
OFF
Alarm is not generated.
Operation of this product will continue when the alarm
WRN
occurs.
FLT
Operation of this product will stop when the alarm occurs.
5.5 Advanced setting mode
5-40
Ambient temperature lower limit alarm
AMB ⇒ LOTMP ( Alternately displayed )
Operation of leakage alarm
WATER ⇒ LERK ⇒ ALARM( Alternately displayed )
Contents
Alarm is not generated.
Operation of this product will continue when the
alarm occurs.
Operation of this product will stop when the alarm
Occurs.
Operation of the contact input signal 1
INP1 ⇒ ALARM( Alternately displayed )
Contents
Initial value
Initial value
HRR Series