HRX-OM-W002
Chapter 4 Starting the Product
To stop the product when only the pump is running, press and hold the [RUN/STOP] key for
approximately 5 seconds.
(When this operation is performed, an alarm "AL27:
Press and hold for
approximately 5 second.
*The time to run the pump can be set within the range of "0 to 9999 seconds". The factory setting is "0
seconds". Therefore, when an alarm occurs, the operation is as in operation mode [1] .the operation
of the pump stops and the product stops. However, if the user sets the pump operation time greater
than 0s, the pump only runs until the circulating fluid discharge temperature reaches a certain value.
The factory setting is set to 40
o
o
5
to 45
. See "5.3.6 Alarm Setting Menu" for details).
C
C
4.2 Starting and Stopping
4-4
ECO
RUN
RUN
ALM
ALM
WRN
WRN
Flash
RMT
RUN
RMT
EXT
AT
RUN/
STOP
RUN/
MENU
STOP
RESET
SEL
RESET
Restart operation when an alarm occurs
Fig 4-4
o
(The cut off temperature can be set by the user within the range of
C
forced a stop
" occurs.)
° F
MPa
MPa
PSI
LPM
LPM
GPM
H
SEC
H
SEC
MENU
ENT
HRR Series