Chapter 5 Display and Setting of Various Functions
 This function controls the offset temperature to the circulating fluid
discharge temperature
 Control range of the circulating fluid temperature is 5.0
 When the circulating fluid temperature is set to 5.0
temperature to -20.0
adjusted to 0.0oC (32.0
Electric conductivity control method
8.
Press the [▼] key. Displays electric conductivity control method setting screen.
* Displayed only when option DM [Electric conductivity control function , DI water
(pure water) piping] is selected.
Without option DM, "8. Electric conductivity control method", "9. Electric conductivity
set value", " 10. Electric conductivity control hysteresis " are not displayed.
RUN
Electric conductivity control method
When option DM is selected, circulating fluid flows to the DI filter via a
solenoid valve to control electric conductivity.
This solenoid valve can be set to always OPEN,or always CLOSED.
The factory setting is "CTRL: Electric conductivity control".
By pressing the [▲], [▼] key, always OPEN, or always CLOSED
can be set.
Selection item
Electric conductivity setting value
9.
Press the [▼] key. Displays electric conductivity setting value setting screen.
* Displayed only when option DM [with electric conductivity control function , DI water (pure
water) piping] is selected.
RUN
5.5 Advanced setting mode
5-24
o
C, the offset temperature is automatically
o
F) depending on the offset mode.
CTRL: Electric conductivity control enabled (initial value)
DI ⇒ CTRL ( Alternately displayed )
Solenoid valve operation
CTRL
The solenoid valve opens and closes
to control the conductivity.
OPEN
Solenoid valve always open
CLSE
Solenoid valve always closed
Electric conductivity setting value
o
o
C to 35.0
C.
o
C and the offset
Unit: μS / cm
HRR Series