7-7-2

Common Variable Area

Specify the address to access each variable.
Variable
address
H'0000
K7DD Status
H'0001 to
Reserved
H'007F
H'0080
Monitored Feature [0] Monitor Ch 1
H'0081
Monitored Feature [0] Monitor Ch 2
H'0082
Monitored Feature [0] Monitor Ch 3
:
:
H'00A4
Monitored Feature [12] Monitor Ch 1
H'00A5
Monitored Feature [12] Monitor Ch 2
H'00A6
Monitored Feature [12] Monitor Ch 3
H'00A7 to
Reserved
H'00FF
H'0100
Measurement Delay Time
H'0101
Measurement Time
H'0102
Internal Trigger Level
Power Line Data Generator User's Manual (N233)
Variable name
This is a monitored value. It is the parameter exclusive to
communications.
It is the data that brings together the status of the K7DD.
Refer to
for details about the bits.
Do not access.
This is a monitored value. This indicates the feature value
set as a monitored feature. 13 types are allocated for each
channel.
H'FFFF to H'008D (-1 to 141)
Default value
Monitored Feature [0]
Monitored Feature [1]
Monitored Feature [2]
Monitored Feature [3]
Monitored Feature [4]
Monitored Feature [5]
Monitored Feature [6]
Monitored Feature [7]
Monitored Feature [8]
Monitored Feature [9]
Monitored Feature [10] Disabled (-1)
Monitored Feature [11] Disabled (-1)
Monitored Feature [12] Disabled (-1)
Do not access.
This is a setting parameter. This indicates the waiting time
from the trigger point to measurement start.
H'0000 to H'1770 (0 to 6000 [CCF])
Default value: H'0000 (0[CCF])
[CCF] is a unit when the feature calculation cycle is 1.
This is a setting parameter. It expresses a time from the
measurement start to the end.
H'0001 to H'1770 (1 to 6000 [CCF])
Default value: H'0001 (1[CCF])
[CCF] is a unit when the feature calculation cycle is 1.
This is a setting parameter. It is the level of the internal
trigger. A trigger point is assumed when the feature value
as the internal trigger source exceeds this variable value.
H'8007 to H'7FF9 (-32761 to 32761 [digit])
Default value: H'7FF9 (32761[digit])
Hexadecimal values are expressed by H'**.
Description
7-7-5 Details about Status Information (P.7-25)
Variable name
Allocated feature (ID)
R.M.S. Voltage (0)
Voltage Fundamental
Amplitude (4)
Voltage Total Harmonic
Distortion (5)
R.M.S. Current (6)
Current fundamental amplitude
(10)
Current Total Harmonic
Distortion (136)
Active Power (137)
Power Factor (140)
Frequency (141)
Disabled (-1)
7 Communications
Setting
reflection
timing
---
---
---
---
Immediately
Immediately
Immediately
7 - 19