3 Installation and Wiring
Checking Connections
After the insertion, pull gently on the wire to make sure that it does not come
off and that the wire is securely fastened to the terminal block.
When you use a stranded wire, make sure that the stranded wire does not
bend or touch the adjacent terminal.
Removing Wires from the Push-In Plus Terminal Blocks
Use the following procedure to remove wires from
the terminal block.
The same method is used to remove stranded
wires, solid wires, and ferrules.
Hold a flat-blade screwdriver at an angle and
insert it into the release hole. The angle should
be between 10° and 15° inclusive.
If the flat-blade screwdriver is inserted correctly,
you can feel the spring in the release hole.
Remove the wire.
Remove the flat-blade screwdriver from the
release hole.
Push-In Plus Terminal Blocks Specifications
 Specifications
Item
Construction
Applicable wires
Applicable wire size
Wire insertion force
Screwdriver insertion force
Wire stripping length
Ferrule length
Current capacity
Number of insertions
3 - 6
<Upper side>
(1)
Push-in compatible with 1-pole 2-terminal crossover wiring
Front-in and front-release
Hands-free
Ferrules, solid wires, and stranded wires
2
2
0.25 mm
to 1.5 mm
(AWG 24 to AWG 16)
8 N max. for AWG 20 wire
15 N max.
*
8 mm
, 10 mm, or 12 mm
8 mm or 10 mm
10 A (per pole)
50 times
Power Line Data Generator User's Manual (N233)
<Lower side>
Flat-blade screwdriver
(2)
(3)
Wire
(3)
Flat-blade
screwdriver
10 to 15°
Flat-blade
screwdriver
Specifications
* Without ferrules
(1)
Wire
(2)
Flat-blade
screwdriver
10 to 15°