7 Communications
Variable
address
H'0103
Internal Trigger Hysteresis
H'0104 to
Reserved
H'01FF
H'0200
Monitored Feature [0] Critical
Threshold-Ch1
H'0201
Monitored Feature [0] Warning
Threshold-Ch 1
H'0202
Monitored Feature [0] Critical
Threshold-Ch2
H'0203
Monitored Feature [0] Warning
Threshold-Ch2
H'0204
Monitored Feature [0] Critical
Threshold-Ch3
H'0205
Monitored Feature [0] Warning
Threshold-Ch3
:
:
H'0248
Monitored Feature [12] Critical
Threshold-Ch1
H'0249
Monitored Feature [12] Warning
Threshold-Ch1
H'024A
Monitored Feature [12] Critical
Threshold-Ch2
H'024B
Monitored Feature [12] Warning
Threshold-Ch2
H'024C
Monitored Feature [12] Critical
Threshold-Ch3
H'024D
Monitored Feature [12] Warning
Threshold-Ch3
H'024E to
Reserved
H'0300
H'0301
Wiring State
H'0302
Current Input Range
H'0303
Voltage Input Range
H'0304
Feature Calculation Cycle
H'0305
Alarm Threshold Calculation
Sensitivity
H'0306 to
Reserved
H'03FF
7 - 20
Variable name
This is a setting parameter. It is the hysteresis of the
internal trigger. After measurement is started by the internal
trigger, measurement continues until the internal trigger
source drops as much as this hysteresis.
H'0001 to H'2710 (1 to 10000 [digit])
Default value: H'000A (10[digit])
Do not access.
These are setting parameters. They are the critical
threshold and warning threshold of the monitored feature
assigned to [0] through [12]. These setting parameters are
addressed for each channel of 1 to 3.
For information on the setting ranges, refer to
Parameters List (P.A-9).
Do not access.
This is a setting parameter. Set the electrical wiring of the
actuator to be monitored.
H'0000: 3P3W2M (default value), H'0001: 3P4W, H'0002:
Single-phase current only
This is a setting parameter.
H'0000: 0 to 5 A (default value), H'0001: 0 to 25 A, H'0002:
0 to 100 A, H'0003: 0 to 200 A, H'0004: 0 to 400 A
This is a setting parameter.
H'0000: 0 to 150 V (default value), H'0001: 0 to 300 V,
H'0002: 0 to 600 V
This is a setting parameter. It is a cycle at which the K7DD
calculates the feature values. Set the parameter according
to the device operation.
H'0001 to H'07D0 (1 to 2000)
Unit 50 msec, Default value: H'0001 (1)
This is a setting parameter. It is an adjustment parameter
for calculating thresholds when performing simplified
threshold settings of the K7DD function.
H'00C8 to H'07D0 (20.0 to 200.0%)
Default value: H'0320 (80.0%)
Do not access.
Description
A-2
Power Line Data Generator User's Manual (N233)
Setting
reflection
timing
Immediately
---
Immediately
---
After
restart
After
restart
After
restart
After
restart
After
restart
---