6 Using K7DD Parameters
fcap
Feature Calculation Cycle
Set the feature calculation cycle.
The calculation cycle (sampling cycle) is 50 ms.
Setting Example:
If the cycle of the application is 5 seconds.
5000 ms ÷ 50 ms = 100
In this case, set the feature calculation cycle to
100.
When using the simplified threshold setting
function, it is necessary to set the value according to the device operation.
Refer to
4-3-2 Conditions to Use (P.4-5) for details.
acof
Alarm Threshold Calculation Sensitivity
Set the alarm threshold calculation sensitivity.
This value is used for calculating the threshold
value at the completion of teaching.
6 - 22
Range of setting values
1 to 2000 (50 ms)
For the maximum setting of 2000, the calculation cycle
is 100 seconds (2000 x 50 ms).
Setting-related page
(3) K7DD Input Setting (P. 2-10) of 2-2 Configuration with the
K7DD Unit Only
4-3 Simplified Threshold Settings (P. 4-4)
Range of setting values
20.0 to 200.0 (%)
Setting-related page
(4) Operation Settings for Alarm Output (P. 2-11) of 2-2
Configuration with the K7DD Unit Only
4-3 Simplified Threshold Settings (P. 4-4)
Power Line Data Generator User's Manual (N233)
Default
value
1
Default
value
80.0 (%)