(9) Do not install the Product close contact with the heating element.
(10) Use a power supply that will reach the rated voltage within 1 second after the power is turned ON.
(11) Do not install the Product near equipment that generates high frequencies or surges.
(12) Make sure that the setting values registered in the Product match the specifications of the load and
special CT that are actually used.
(13) Do not ground the terminal on the output side of the special CT. Failure to do so may result in
unstable measurement.
(14) Do not directly clamp the special CT to the lines exceeding 600 VAC.
(15) If an error occurs during the operation of the Product, stop the operation immediately and make
suitable corrections such as replacement.
(16) Do not use any liquids such as paint thinner, similar solvents or alcohol to clean the Product. Clean
it with a soft, dry cloth.
Regulations and Standards

Conformance to Safety Standards

• The protection provided by the device may be impaired if the device is used in a manner that is
not specified by the manufacturer.
• To use the Product, install it as an embedded device within a control panel.
• To use the special CT, install it in the same control panel as the Product with a sufficient clearance
from other devices.
• For the special CT, use one with –C suffixed to the model.
• For the operation power supply and voltage inputs, use recommended fuses that are externally
installed.
• Use the voltage and CT inputs under conditions specified for the measurement category.
• The maximum temperature of the terminal block is 65°C. Therefore, use wires with a rated
temperature of 65°C or higher.
• Select wires in accordance with Table 2 so that the case temperature of the special CT will be
65°C or less.
• For the wire passing through the primary side of the special CT, use an insulated wire with basic
insulation or higher degree of insulation that conforms to the rated voltage and size of the AWM
(Appliance Wiring Material) wire in Table 1.
• Table 1 below shows the nominal voltage and measurement circuit connections available for each
measurement category in the Main Power Supply System Configurations. Do not use the device
under conditions that exceed this category and conditions.
Power Line Data Generator User's Manual (N233)
Regulations and Standards
9