Wiring
6.4

Wiring procedure

6- ][Verdr_Vorgehensweise
Wiring procedure
6400
Wiring procedure
6.4
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
The following guidelines are intended to help you carry out the electrical
installation in a sensible order, without forgetting anything important.
Choice of cable
Select cables in accordance with EN 60204
Earthing, shielding
Make sure that shielding and earthing are EMC-compliant
Earth the mounting plate, the motor housing and the control system's
ground terminal. Information on the connection technology can be
found under "Block diagram".
Wiring
Lay the power and control cables separately
Incorporate the relay output for operational readiness (BTB) into the
plant's safety circuit
Connect the servo amplifier's digital inputs and outputs
Connect the AGND earth (even if a fieldbus is used)
If necessary, connect the analogue setpoint value
Connect the encoder (feedback)
Connect the expansion card
Connect the motor cables
Connect the shielding on both ends; use a motor choke if the cable
runs are over 25 m
Connect the motor holding brake, connect the shielding on bothends
If necessary, connect the external brake resistor (with fuse protection)
Connect the 24 VDC supply voltage (for maximum permitted voltage
values see chapter entitled "Technical Details")
Connect the mains voltage (for maximum permitted voltage values
see chapter entitled "Technical Details"); for information on FI residual
current devices see section entitled "Residual current devices")
Connect the PC (see section entitled "Communications interfaces")
Check
Check the wiring against the wiring diagrams