Stop And E-Stop Functions; Stop Functions - Pilz PMCtendo DD5 Operating Manual

Servo amplifiers
Hide thumbs Also See for PMCtendo DD5:
Table of Contents

Advertisement

3
Safety
3.4

Stop and E-STOP functions

3.4.1

Stop functions

3-
Stop and E-STOP functions
3400
Stop and E-STOP functions
3.4
3- ][Sicherheit_Stopp
Stop functions
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
3-8
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
The stop function is used to bring the machine to a standstill in normal
operation.
The stop functions are defined in EN 60204-1 (VDE 0113), paragraphs
9.2.2, 9.2.5.3.
Category 0
Stopping by immediate removal of power to the machine actuators (un-
controlled stop).
Category 1
A controlled stop, with power to the machine actuators available to
achieve the stop and then removal of power when the stop is achieved.
Category 2
A controlled stop, with power left available to the machine actuators.
The stop category shall be determined from the hazard analysis of the
machine.
Appropriate measures to ensure a reliable stop are also required.
Category 0 or 1 stops shall be operational regardless of the operating
mode. A Category 0 stop shall take priority. Stop functions shall operate
by de-energising the relevant circuit and shall override related start func-
tions.
Where required, facilities to connect protective devices and interlocks
shall be provided. Where applicable, the stop function shall signal that
such a condition exists. The reset of the stop function shall not initiate
any hazardous conditions.

Advertisement

Table of Contents
loading

Table of Contents