6
Wiring
6.1

General wiring guidelines

6- Verdr_Allgemein_S1_S2
General wiring guidelines
6100
General wiring guidelines
6- 6.1
Wiring
Wiring
6 6 000
Verdr_Leiterquerschnitte
Verdr_Leitungslaengen
Inputs
Appropriate wiring must be used to exclude short circuits between
the inputs or to a supply line!
Signal lines must be shielded.
Outputs
If short circuits occur between the cable from the output to the load
and a supply line, it will no longer be possible to switch off the load.
Possible remedy: Exclude the error by using separate multicore ca-
ble for supply voltages
Use appropriate wiring to exclude short circuits between the outputs!
Signal lines must be shielded.
The outputs do not need suppression for inductive loads.
Cable material
Use copper wiring.
Please note:
Cable cross sections for field connection terminals in mm
– Digital inputs/outputs, supply voltage: 0.5 (AWG20) ... 1.0
(AWG18), AEH without plastic collar, in accordance with DIN
46228/1
Max. cable lengths
– Supply voltage: Max. 30 m
– Digital inputs and outputs: Max. 30 m
2
:
6-1