Replacing the cooling unit power cord on a Multiservice
Switch 7480
Prerequisites
Procedure steps
NN10600-175 6.1S2
Replace the power cord on the cooling unit for a Nortel Networks
Multiservice Switch 7480 if it fails.
CAUTION
Risk of equipment damage
Replace a cooling unit power cord and restart cooling
units within 10 minutes. You can damage the CPs and
FPs and they can fail if the cooling fans are off longer
than 10 minutes.
You need a replacement cooling unit power cord with PEC NTHR66BA.
1
Disconnect the power cord from the "C.U. Power" connector on the back
of the shelf assembly. Use a 1/8-in. screwdriver to loosen the two screws.
See the figure "Cooling unit power cord" (page 501).
2
Connect the replacement power cord to the "C.U. Power" connector on the
back of the shelf assembly. Use a 1/8-in. screwdriver to tighten the two
screws.