Kt/Km Electrical Connection - AUMA SAEx 07.2 Operation Instructions Manual

Multi-turn actuators
Hide thumbs Also See for SAEx 07.2:
Table of Contents

Advertisement

SAEx 07.2
SAEx 16.2 / SAREx 07.2
6.3.

KT/KM electrical connection

Short description
Technical data
SAREx 16.2
Figure 20: KT/KM electrical connection
[1]
Terminal carrier with screw-type/spring clamp terminals
[2]
Connection frame
Figure shows KT version
KT plug-in electrical connection with screw-type terminals for power connection and
spring clamp terminals for control contacts.
KM version with additional support terminals (terminal blocks) via terminal carrier.
Both versions (KT and KM) are available with terminal compartment in protection
type Ex e (increased safety) as well as in protection type Ex d (flameproof enclosure)
(refer to Ex marking on name plate).
Plug-in connection is made via the connection frame. For cable connection, simply
remove the cover. The connection frame with the cable entries remains within the
device. The flameproof interior of the connected devices remains sealed.
Table 11:
KT/KM/KL electrical connection
No. of contacts max.
Designations
Support terminals max.
Connection voltage max.
Rated current max.
Type of customer connection
Connection diameter max.
1)
Four protective earth connections within frame
2)
The sum of the currents of all control contacts must not exceed 50 A.
Power contacts
1)
6 + PE conductors
U1, V1, W1, U2, V2, W2,
3
1,000 V
25 A
Screw connection
PE = Ring lug/U-bracket
2
10 mm
Electrical connection
Control contacts
50
1 to 36, 37 to 50
12
250 V
2)
5 A
Spring clamp terminals
2
2.5 mm
25

Advertisement

Table of Contents
loading

This manual is also suitable for:

Saex 16.2Sarex 07.2Sarex 16.2

Table of Contents