Marking Of Iop Room - C-DOT DSS MAX-XL Installation Manual

Table of Contents

Advertisement

Basemount assemblies of the first suite will be placed on the first and second
suite line. Basemount assemblies of the second suite will be placed on the
third and fourth suite line and so on.
A typical MAX-XL switch room layout for a five suite configuration is shown
in Fig. 1.4. It is to be noted that number of suites required depends on the
capacity and configuration of the switch.
A typical TAX-XL switch room layout for a 6K trunk configuration is shown
in Fig. 1.4 (a). For higher capacity (>6K) TAX one more suite will be added
and CM will then be installed in third suite.
1.6.

MARKING OF IOP ROOM

Datum lines are drawn in the IOP room as per the procedure adopted above. Refer
Fig. 1.5. Marking of IOP lines has to be made in such a way that the clearance
between the two IOPs is not less than 750 mm, and also the clearance between the
wall and any of the two IOPs is not less than 750 mm. IOP-PDP is also mounted in
the IOP room for the distribution of DC power to the IOPs.
For marking of IOP-PDP position in IOP room, draw a line parallel to second datum
line at a distance of 150 mm away from it. Next draw a line perpendicular to the
second datum line at a distance of 500 mm from the first datum line. The placement
of IOPs, console tables and IOP-PDP are shown in Fig. 1.5.
INSTALLATION MANUAL
FLOOR MARKING
15