Dc Cables - C-DOT DSS MAX-XL Installation Manual

Table of Contents

Advertisement

10.5. DC CABLES

Fig. 10.7 (a), Fig. 10.7 (b), Fig. 10.7 (c) and Fig. 10.7 (d) show Block Diagram of DC
Power Cables.
10.5.1.
Details of -48V & -48V GND DC Cable from Switching Cubicle to IDP
CDOT ASSY NO.
DRAWING NO.
CABLE PART NO.
CABLE MARKER NO.
CABLE SPECIFICATION
CABLE UNIT COLOUR CODE
CABLE LENGTH
SOURCE TERMINATION PART NO.
DESTINATION TERMINATION NO.
SOURCE
DESTINATION
ASSEMBLY PROCEDURE
Note :
Three such cables (blue) for -48V and three (Red) for -48V GND will run
parallely from switching cubicle to IDP. See Fig. 10.7 (a).
Two bus bars of size 100x10 mm will run parallely from switching cubicle to
IDP, each bus bar is for -48 V and -48 V GND.
Refer Fig. 10.7 (a) for block diagram.
INSTALLATION MANUAL
CABLE PREPARATION AND LAYING
:
ACB-MAXLPPSI-000 (Blue)
ACB-MAXLPGSI-000 (Red)
:
Fig. 10.8
:
MCA-PVCSCP36-401 (Blue)
MCA-PVCSCP16-401 (Red)
:
PPSI (Blue) PGSI (Red)
:
Power cable, Single core 240mm
:
Blue & Red
:
Site dependent
:
MCT-ERTCH014-401 300mm
Cu Tube Terminal Crimp Type
:
MCT-ERTCH014-401 300mm
Cu Tube Terminal Crimp Type
:
Switching Cubicles
:
IDP
:
Crimping tool SYD-20
Die to be used JDD-11
OR
2
-
2
-
2
115