SL.
C-DOT ASSY NO
No.
1.#
ACB-MAXLGEM1-000
2.
ACB-MAXLGDS1-000
3.
ACB-MAXLGDS2-000
4.
ACB-MAXLGR01-000
5.
*ACB-MAXLGM01-000
6.
ACB-MAXLGM02-000
7.
ACB-MAXLGMP1-000
8.
ACB-MAXLGCD1-000
9.
ACB-MAXLGCD2-000
10.
ACB-MAXLGCI1-000
Note :
#
*
INSTALLATION MANUAL
DRAWING
NO.
FIG. 10.2
FIG. 10.2
FIG. 10.2
FIG. 10.2
FIG. 10.3
FIG. 10.3
FIG. 10.3
FIG. 10.3
FIG. 10.3
FIG. 10.3
Instead of 240mm
2
There will be two such cables running between Earth collector plate
and MDF (lines).
TABLE 10.1
FROM
Earth Pit
Earth
Collector Plate
Earth Collector Plate
DCDP1 digital
ground bus bar
Earth Collector Plate
DCDP2 Digital
ground bus bar
Earth Collector Plate
Switching
Cubicle-48V
Gnd Bus Bar
Earth Collector Plate
MDF (Lines)
Earth Collector Plate
MDF (Trunks)
Earth Collector Plate
MDF (PCM)
Earth Collector Plate
DCDP1
Chassis
ground bus-bar
Earth Collector Plate
DCDP2
Chassis
ground bus-bar
Earth Collector Plate
IDP chassis
cables BTC wire (19/1.8mm
CABLE PREPARATION AND LAYING
TO
SIZE
#240mm
240mm
240mm
240mm
25mm
25mm
25mm
25mm
25mm
25mm
) can be used.
2
CABLE
MARKER
GEM1
2
GDS1
2
GDS2
2
GR01
2
GMO1
2
GMO2
2
GMP1
2
GCD1
2
GCD2
2
GCI1
2