10.5.4.
Detail of -48V and -48V GND DC Cables from DCDP to PDP
CDOT ASSY NO.
DRAWING NO.
CABLE PART NO.
CABLE MARKER NO.
CABLE SPECIFICATION
CABLE UNIT COLOUR CODE
CABLE LENGTH
SOURCE TERMINATION PART NO.
DESTINATION TERMINATION NO.
SOURCE
DESTINATION
ASSEMBLY PROCEDURE
Note :
XX takes different values as depicted in Table 10.5.
Refer Fig. 10.7 (b) & (c) for Block Diagrams.
INSTALLATION MANUAL
CABLE PREPARATION AND LAYING
:
ACB-MAXLPLXX-000
ACB-MAXLPNXX-000
:
Fig. 10.11
:
MCA-PVCSCP33-401 (Blue)
MCA-PVCSCP13-401 (Red)
:
PLXX (Blue)
PNXX (Red)
:
Power cable, Single core 120mm
:
As per Table 10.5
:
Site dependent
:
MCT-ERRIN421-401 150mm
Ring Terminal Crimp Type
:
MCT-ERRIN421-401 150mm
Ring Terminal Crimp Type
:
As per Table 10.5
:
As per Table 10.5
:
Crimping tool SYD-20
Die to be used JDR-13
2
-
2
-
2
127