Configuration variable
Latching time
Unlatch the output
Manual Operation:
Output status
(17)
Functions 0x01 and 0x05 are used for this variable.
7�3�10�7�- Digital Output 2
Configuration variable
Variable
Maximum value / Energy per
pulse
Minimum value
Connection delay
High level pulse width
Disconnection delay
Low level pulse width
Hysteresis
Contact status
Latch
Latching time
Unlatch the output
Manual Operation:
Output status
(19)
Functions 0x01 and 0x05 are used for this variable.
7�3�11�- CLEAR PARAMETERS
Parameters are cleared by Function 05: writing a relay.
Clear energies and counters
Clear maximum and minimum values
Clear Maximum Demand values
Clear the Maximums values of the Maximum Demand
Clear all (Energy Meters, maximums and minimums, Quality Parameter
Meters, Maximum Demand and Maximum Demand maximums)
Clear energy meters
Clear quality parameters
94
Table 34 (Continued): Modbus Memory Map: Digital Output 1�
Format
Uint [16]
(18)
Bool
Bool
(18)
Table 35: Modbus Memory Map: Digital Output 2�
Format
Uint [16]
Float [32]
Float [32]
Uint [16]
Uint [16]
Uint [16]
Uint [16]
Bool
Uint [16]
(19)
Bool
Bool
(19)
Table 36: Modbus Memory Map: Clear parameters�
Clear parameters
Digital Output 1
Address
Valid data range
4E2A
7530
ON(connected output): FF00
7539
OFF (disconnected output): 0000
Digital Output 2
Address
Valid data range
Table 10 - Table 11 - Table 12 -
4E34
Table 13 - Table 14
4E36-4E37
Depends on the selected variable
4E38-4E39
Depends on the selected variable
4E3A
0... 999 ms (x10)
4E3B
0... 999 ms (x10)
4E3C
0: Normally open -
4E35
1: Normally closed
4E3D
4E3E
7544
ON(connected output): FF00
754D
OFF (disconnected output): 0000
0... 65499 s
0
0... 65499 s
0... 65499 s
0... 99%
0: No - 1: Yes
0... 65499 s
0
Format
Address
Bool
834
Bool
837
Bool
83E
Bool
83F
Bool
848
Bool
849
Bool
2B5C
Instruction Manual
line-CVM-D32
Default value
0 s
0
0
Default value
0
-
-
0 s
0 s
0%
0
0 s
0
0
Value to
be sent
0xFF00
0xFF00
0xFF00
0xFF00
0xFF00
0xFF00
0xFF00