4.9.6
Cabinet illumination with service socket (option L50)
Description
A universal lamp with an integrated service socket is installed in each cabinet panel. The
power supply for the cabinet illumination and socket must be provided externally and fused
at max. 10 A. The cabinet illumination is switched on manually via a slide switch or
automatically by means of an integrated motion detector (factory setting). The mode is
selected via the switch on the light.
Connection
Table 4-24
Terminal
Max. connectable cross-section: 4 mm
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Terminal block X390 – connection for cabinet illumination with service socket
Designation
1
L1
2
N
3
PE
Technical specifications
230 V AC
(AWG 10)
2
Electrical installation
4.9 Other connections
75