Electrical installation
4.9 Other connections
4.9.9

EMERGENCY STOP category 1; 230 V AC (option L59)

Description
EMERGENCY STOP category 1 for controlled stop to EN 60 204. This function stops the
drive by means of a quick stop along a deceleration ramp that must be parameterized. The
cabinet unit is then disconnected from the power supply via the line contactor, which
bypasses the electronics by means of a safety combination (to EN 60 204-1).
The operating status is indicated by means of eight LEDs (-A120, -A121).
Connection
Table 4-27
Terminal
Max. connectable cross-section: 4 mm² (AWG 10)
Setting
When the quick stop function (OFF3 ramp-down time, p1135) is used to shut down the drive,
the ramp-down time should be less than (or at the most equal to) the time set on the
contactor safety combination, after which the converter is de-energized.
Diagnosis
Messages output during operation and in the event of faults (meaning of LEDs on -A120, -
A121) are described in "Additional Operating Instructions" in the operating manual.
78
Terminal block X120 – connection for EMERGENCY STOP category 1 (230 V AC)
7
8
15
16
17
18
Technical specifications
Loop in EMERGENCY STOP button from line side,
remove jumpers 7-8.
"On" for monitored start:
Remove jumpers 15–16 and connect button.
Checkback "trip safety combination"
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A