Siemens SINAMICS S150 Operating Instructions Manual page 227

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Scalings for vector object
Table 6-19
Scalings for vector object
Size
Reference speed
Reference voltage
Reference current
Reference torque
Reference power
Reference frequency
Reference modulation depth
Reference flux
Reference temperature
Object A_INF
Table 6-20
List of signals for the operation screen - object A_INF
Signal
DC link voltage smoothed
Input voltage
Active current
Line frequency
Active power
Actual value of current
Temperature of power unit
Power factor, smoothed
Modulation depth, smoothed
Reactive current component smoothed
Scalings for object A_INF
Table 6-21
Scalings for object A_INF
Variable
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation depth
Reference temperature
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = p2003
100 % = r2004
100% = p2000/60
100 % = Maximum output voltage without overload
100 % = Rated motor flux
100% = 100°C
Parameters
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
Scaling parameter
100 % = p2000
100 % = p2001
100 % = p2002
100 % = r2004
100 % = Maximum output voltage without overload
100% = 100°C
Short name
r0026
U_DC
r0025
U_IN
r0030
IACTV
r0024
FLINE
r0032
PACTV
r0027
I_IST
r0037
T_LT
r0032
PACTV
r0028
AUSST
r0029
IREAC
6.7 Control via the operator panel
Default for quick commissioning
p2000 = Maximum speed (p1082)
p2001 = 1000 V
p2002 = Current limit (p0640)
p2003 = 2 x rated motor torque
r2004 = (p2003 x p2000 x π) / 30
Unit
Scaling (100 %=...) See
table below
V
p2001
V
p2001
A
p2002
Hz
p2000
kW
r2004
A
p2002
°C
Reference temperature
kW
r2004
%
Reference modulation
depth
A
p2002
Default for quick
commissioning
p2000 = p0211
p2001 = r0206/r0207
p2002 = r0207
r2004 = r0206
Operation
227

Advertisement

Table of Contents
loading

Table of Contents