Siemens SINAMICS S150 Operating Instructions Manual page 371

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Figure 9-24
The maximum inclination (r
LU/s
permanently, set parameter p2575 ("Active jerk limitation") to 1. In this case, limitation
cannot be activated or deactivated in traversing block mode by means of the command
"JERK" as this would require parameter p2575 ("Activate jerk limitation") to be set to zero.
The status signal r2684.6 ("Jerk limitation active") indicates whether or not jerk limitation is
active.
Limitation is effective:
● In jog mode
● When traversing blocks are processed
● When setpoints are defined directly/MDI for positioning and setup
● during referencing
● During stop responses due to alarms
Jerk limitation is not active when alarms occur with stop responses OFF1 / OFF2 / OFF3.
Function diagram
FD 3630
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Jerk limitation activated
for both acceleration and braking. The resolution is 1000 LU/s
3
Traversing range limits
Functions, monitoring, and protective functions
) can be set in parameter p2574 ("Jerk limitation") in the unit
k
9.4 Extended functions
. To activate limiting
3
371

Advertisement