Table 12-21 Version A, 500 V – 690 V 3 AC, part 3
Category
Order No. 6SL3710-
Rated motor output
Rated input voltage
Rated input current
1)
Rated output current
Base-load current I
2)
L
Base-load current I
H 3)
Max. output frequency
4)
Power loss
Cooling air requirement
Sound pressure level at 50/60 Hz
Line connection
Recommended: DIN VDE
Maximum: DIN VDE
AWG/MCM
Fixing screw
Motor connection
Recommended: DIN VDE
Maximum: DIN VDE
AWG/MCM
Fixing screw
Protective conductor connection
Fixing screw
Approx. weight (standard version)
Frame sizes
Active Interface Module
Active Line Module
Motor Module
Dimensions (standard version)
Width x height x depth
Recommended protection
Line protection
(with option L26)
Rated current
Frame size to DIN 43620-1
Line and semi-cond. protection
(without option L26)
Rated current
Frame size to DIN 43620-1
The currents are based on a power factor of cos ϕ = 1 and include 10 A for the external auxiliary equipment (as used, for
1)
example, with options L19 or B03).
The base-load current (I
2)
(see "Overload capability").
The base-load current (I
3)
(see "Overload capability").
Maximum output frequency at factory-set default pulse frequency (for information on increasing the output frequency,
4)
see "Functions, monitoring and protective functions/Increasing the output frequency"; for information on derating data, see
"Derating data").
The recommendations for the North American market in AWG or MCM must be taken from the appropriate NEC
5)
(National Electrical Code) or CEC (Canadian Electrical Code) standards.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Unit
7LG32-6AA0
kW
250
V
A
242
A
260
A
250
A
233
Hz
100
kW
11.1
m³/s
1.19
dB(A)
75/77
mm
2 x 95
5)
2
mm
4 x 240
2
4 x (500)
M12 (2 holes)
mm
2 x 95
5)
2
mm
2 x 185
2
2 x (350)
M12 (2 holes)
M12 (2 holes)
kg
892
GI
GX
GX
mm
1600 x 2,000 x 600
3NA3354-6
A
355
3
3NE1331-2
A
350
2
) is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s
L
) is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s
H
7LG33-3AA0
315
500 V to 690 V 3 AC ± 10% (-15% < 1 min)
304
330
320
280
100
12.5
1.19
75/77
2 x 120
4 x 240
4 x (500)
M12 (2 holes)
2 x 120
2 x 240
2 x (500)
M12 (2 holes)
M12 (2 holes)
892
GI
GX
GX
1600 x 2,000 x 600
3NA3365-6
500
3
3NE1334-2
500
2
Technical specifications
12.3 Technical specifications
7LG34-1AA0
400
375
410
400
367
100
17.7
1.96
77/79
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
2 x 185
4 x 240
4 x (500)
M12 (2 holes)
M12 (2 holes)
1716
HI
HX
HX
2200 x 2,000 x 600
3NA3365-6
500
3
3NE1334-2
500
2
495