Harmonics Controller - Siemens SINAMICS S150 Operating Instructions Manual

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Functions, monitoring, and protective functions
9.2 Active Infeed functions
Parameters
• p3410
• r3411
• r3412
• p3421
• p3422
• p3620
• p3622
9.2.2

Harmonics controller

Description
Harmonics in the supply voltage cause harmonics in the line currents. Current harmonics
can be reduced by activating the harmonics controller.
Example: setting the harmonics controller
The 5th and 7th harmonic are to be compensated:
Table 9-1
Index
[0]
[1]
0% scaling means that the harmonics controller has been deactivated.
100 % scaling means that the harmonics controller has been activated with standard gain.
The phase currents in parameter p0069[0...2] (U, V, W) can be verified using the STARTER
trace function.
Parameters
• r0069[0...6]
• p3624[0...1]
• p3625[0...1]
304
Infeed identification method
Infeed identified inductance
Infeed DC-link capacitance identified
Infeed DC link capacitance
Reference variable of technological unit
Infeed current controller adaptation lower application threshold
Infeed current controller adaptation reduction factor
Sample parameters for the harmonics controller
p3624 Infeed harmonics controller
order
5
7
Phase current, actual value
Infeed harmonics controller order
Infeed harmonics controller scaling
p3625 scaling
100 %
100 %
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A

Advertisement

Table of Contents
loading

Table of Contents