Siemens SINAMICS S150 Operating Instructions Manual page 166

Converter cabinet units 75 kw to 1200 kw
Hide thumbs Also See for SINAMICS S150:
Table of Contents

Advertisement

Commissioning
5.5 First commissioning
Basic commissioning: Entering the basic parameters
166
Entering the basic commissioning
parameters:
If a sinusoidal filter (option L15) is
connected, it must be activated in p0230
(p0230 = 3) otherwise it could be
destroyed.
p0700: Preset command source
5: PROFIdrive
6: TM31 terminals
7: Namur
10: PROFIdrive Namur
p1000: Preset setpoint source
1: PROFIdrive
2: TM31 terminals
3: Motorized potentiometer
4: Fixed setpoint
Once a setpoint source has been
selected (p1000), the main setpoint
p1070 is defaulted accordingly.
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
To change a parameter value, navigate
to the required selection field and
activate with <F5>.
Another window appears in which you
can
- enter the required value directly, or
- select the value from a list.
Final confirmation
Confirm the basic parameters to save
them.
Once you have selected "Continue" and
activated your entries with <F5>, the
basic parameters you entered are
permanently saved and the calculations
required for closed-loop control are
carried out.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A