Commissioning
5.5 First commissioning
Basic commissioning: Selecting the motor type and entering the motor data
Note
The steps described below also apply to induction motors.
When commissioning a permanent-field synchronous motor (p0300 = 2), there are a few
special conditions that apply, which are detailed in a separate chapter (see "Setpoint
channel and closed-loop control/Permanent-field synchronous motors").
162
You can select the motor standard and
type in the dialog screen.
The following is defined for the motor
standard:
0: Line frequency 50 Hz, motor data in kW
1: line frequency 60 Hz, motor data in hp
The following selection options are
available for the motor type:
1: Induction motor
2: Permanent-field synchronous motor
5: Synchronous motor (separately-excited)
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
Entering motor data specified on the type
plate
To navigate through the selection fields,
choose <F2> or <F3>.
To activate a selection, choose <F5>.
To change a parameter value, navigate to
the required selection field and activate
with <F5>.
The system displays another window in
which you can:
• Enter the value directly, or
• select the value from a list.
When you have finished entering the motor
data, choose "Continue" underneath the
final parameter value and activate your
entries with <F5>.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A