3. Enter a project name and, if necessary, the author, memory location and a comment.
4. Click Continue > to set up the PG/PC interface.
Figure 5-5
Note
The online connection to the drive unit can only be established via PROFIBUS.
5. Click Change and test... and set up the interface in accordance with your device
configuration.
The Properties..., Copy..., and Select... pushbuttons are now active.
Drive converter cabinet units
Operating Instructions, 07/07, A5E00288214A
Set up interface
5.3 Procedure for commissioning via STARTER
Commissioning
121