Option LED States

The option has four LEDs:
• Bi-color Status LEDs:
– Module status (MS) red/green
– Network status (NS) red/green
• Ethernet Port LEDs (2 each):
– Network speed-10/100 green
– Link status and network activity-Link/Act green
A - 1000-Series, Z1000U
B - GA500, GA700, GA800, CR700
*1
LED label has transparent background and white letters. Please make sure that you use the correct label for Z1000, HV600, or
FP605.
Wait 2 seconds minimum for the power-up diagnostic process to complete before you verify the LED states.
4.2
shows the operating status of the option LEDs after the power-up diagnostic LED sequence is complete. The
number in parentheses in the "Display" column is the number of pulses of 250 ms ON and 250 ms OFF. When the
ON and OFF pulses complete for the number of times in parentheses, LED will be 500 ms OFF, then repeat the
cycle of ON and OFF for the number of times.
Refer to
Table
4.3for more information about the LEDs.
LED Name
MS
NS
*1
10/100
YASKAWA SIEP C730600 0KA PROFINET Technical Manual
Figure 4.2 Option LED Labels
Table 4.2 Option LED States
Indication
Color
Display
-
OFF
Green
ON
Green
Flashing (1)
Green
Flashing (2)
Red
ON
Red
Flashing (2)
Red
Flashing (3)
Red
Flashing (5)
Red/Green
Flashing
-
OFF
Green
ON
Green
Flashing
Red
Flashing (1)
Red
Flashing (2)
Red
Flashing (3)
Green
OFF
C - Z1000, HV600, FP605
Operating State
Power supply off
Option operating
Diagnostics
Configuration tool
Default MAC or bad webpage
configuration.
No IP (non-fatal)
No station name (non-fatal)
EF0 (Forced Fault)
Option self-test
Power supply OFF or Offline
Connected
Connected and stopped
Lost communication
Lost link
IP configuration error
10 Mbps is established
4 Option Components
*1
Description
There is no power to the drive.
The option is operating normally and
initialization is complete.
Diagnostic data available.
Set by the hardware configuration tool for
identification purposes.
The default MAC address is programmed
or the option detected an issue with the
webpage configuration.
No IP address assigned.
No station name assigned.
Forced fault from the network.
The option is in self-test mode.
-
Connection established with IO-Controller
and in RUN mode.
Connection established with IO-Controller
and in STOP mode.
Host communication is temporarily lost.
No link detected to network.
The configured IP addresses are
incompatible. The IP Address (F7-01 to
F7-04) does not agree with the Subnet
Mask (F7-05 to F7-08) and/or the
Gateway Address (F7-09 to F7-12).
This will clear the fault automatically.
-