WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv
4.2

Status bytes

Status bytes are identically implemented for all channels. Therefore, the following
description in this section applies to all status bytes of the I/O module.

Table 18: Status byte CH1_S0

Bit 7
RegCom
Underrange
Overrange
User
Underrange
User Overrange
Overload*
Wire Break**
General Error
RegCom
* only for signal type 0 ... 20 mA, 4 ... 20 mA, ± 20 mA und 3,6 ... 21 mA
** only for signal type 4 ... 20 mA und 3,6 ... 21 mA
All manuals and user guides at all-guides.com
Status byte CH1_S0, Byte 0
Bit 6
Bit 5
Bit 4
General
Wire
Overload
Error
Break
Underrange
0:
The field-side input voltage or current are above the measurement range
lower limit.
1:
The field-side input voltage or current are below the measurement range
lower limit.
Overrange
0:
The field-side input voltage or current are below the measurement range
upper limit.
1:
The field-side input voltage or current are above the measurement range
upper limit.
User Underrange
0:
The field-side input voltage or current are above the measurement range
lower limit parameterized by the user.
1:
The field-side input voltage or current are below the measurement range
lower limit parameterized by the user.
User Overrange
0:
The field-side input voltage or current are below the measurement range
upper limit parameterized by the user.
1:
The field-side input voltage or current are above the measurement range
upper limit parameterized by the user.
Overload
0
No overload
1
Overload in sensor cables
Wire Break
0
No wire break
1
Wire break in sensor cables
Group Error
0:
No error, bit 0 (underrange), bit 1 (overrange), bit 4 (overload) and bit 5
(wire break) is not set.
1:
Error, bit 0 (underrange), bit 1 (overrange), bit 4 (overload) and bit 5 (wire
break) is set.
Register Communication
0:
Register communication is switched off (normal mode).
1:
Register communication is switched on.
Process Image
Bit 3
Bit 2
User
User Under-
Overrange Underrange
Overrange
range