Commissioning
7.1.3.3

Scaling

The settings entered in the "Scaling" dialog window directly affect the process
value. Scaling is carried out for each channel and is saved permanently, i.e.
available after restarting the node.

Figure 19: Parameter "Scaling"

To select the process value for the respective channel, select the corresponding
tab [Channel 1] ... [Channel 4].

Table 34: "Scaling" Parameters

Selection/Control Field Possible Settings
Manufacturer scaling
User scaling
Process value
Manual
Version 1.0.0
All manuals and user guides at all-guides.com
Can be switched on or off; the gain and offset values
cannot be changed.
When user scaling is switched on, the user can enter
values for offset and gain.
The register values can be represented and edited as
either decimals or hexadecimals. If the user scaling is
deactivated, the offset and gain values cannot be
changed.
Offset The offset value causes a zero offset of the
process value (shift along the Y axis). The
value entered must fall within the range −32768
to 32767.
Gain
The gain value is used as a gain factor applied
to the process value.
The value entered must fall within the range
−2.0000 to 1.9999.
The resolution 1/16384 has already been taken
into account for the decimal entry.
The process value can be constant or deliberately kept
changeable;
it can be represented as a fixed decimal value with unit
or as a hexadecimal to correspond with the
measurement range.
WAGO-I/O-SYSTEM 750
750-471 4AI U/I Diff Galv